DS2100 User's Manual
SECTION 2: SAFETY & EMC INSTRUCTIONS
PAGE 2-26 C27750-001
2.4 UL Requirements
Detailed below are the specific UL requirements for the DS2100.
2.4.1 Specific UL Requirements
Usage: The DS2100 shall be used according to the guidelines given in this manual.
Ratings: The DS2100 shall be used within the ratings specified in the markings on the equipment.
24V Logic Supply: The 24V supply is intended for use in the secondary of a Class 2 supply. Alternatively, it
should be additionally fitted with a Listed current limiting fuse, rated 3A on the supply input to the device.
Surrounding Air Temperature:- “Maximum Surrounding Air Temperature, 40
o
C”.
Pollution Degree 2 Installation:- The drive must be installed in a Pollution Degree 2 environment.
Equipment Designation: - Open Type Equipment.
Short circuit Ratings:-
DS2100 3/11, 6/22, 8/22, 14/42, 20/45, 25/70, 30/90, 50/140: “Equipment suitable for use on a circuit capable
of delivering not more than 5000 rms symmetrical Amperes, 460V ac + 10% Maximum”.
DS2100 60/180, 100/300: “Equipment suitable for use on a circuit capable of delivering not more than 10000
rms symmetrical Amperes, 460V ac + 10% Maximum”.
Branch Circuit Protection. The Branch Circuit Protection for short circuit protection shall be provided in the end
use application by external fuses. Recommended fuses are manufactured by Cooper Bussmann.
DS2100 3/11 & 6/22: Fuse Model No. FWP-25A14F Semiconductor Type Fuses.
DS2100 8/22 & 14/42: Fuse Model No. 50FE Semiconductor Type Fuses.
DS2100 20/45, 25/70 30/90: Fuse Model No: 100FE Semiconductor Type Fuses.
DS2100 50/140 & 60/180: Fuse Model No: 160FEE Semiconductor Type Fuses.
DS2100 100/300 : Fuse Model No: 315-FM Semiconductor Type Fuses.
Wiring. The drive shall be wired with stranded and \ or solid copper (Cu), 60/75
o
C conductors only. The tightening
torque for terminal blocks specified in Section 3 of this manual shall be applied. These requirements do not apply to
the control circuit terminals.
Regeneration Resistor. The regeneration resistor, when external, shall be wired with R/C (AVLV2) rated wire or
shall be insulated with R/C (YDPU2) or R/C (UZCW2) rated insulation.
Field Wiring. The power connector of the DS2100 µA (J6) is not rated as a Field Wiring Terminal. This connector
may only be used as a Factor Wiring Terminal block.
Over-speed Protection: The DS2100 incorporates a software-based over-speed protection. See ‘Motor Rating
Parameters’ and ‘Velocity Limiting’ in Section 5 of this Manual.